TeSys GV motor circuit breaker, 3 poles (3P), 150A/690V, for protection of 3-phase motors 55-75kW@400V. It provides thermal magnetic protection and additional protections, breaking capacity Icu 70kA, start-stop control by rotary handle, connection for bars or cables with lugs (direct connection of cables with additional connectors). Thermal protection adjustable by dials with a setting current Ir in range 70-150A and a selectable tripping class 5, 10 or 20, magnetic protection at 15 In. Additional protections with fixed pick-up include short time delay protection Isd at 13 Ir, phase unbalance and loss protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Product Attributes
Attribute
Value
brand
Schneider Electric
This item is sold on RFQ only. Click on "Get Quote" to raise RFQ
The Get Quote feature allows you to select the product you need and request for a quotation.
To Request for a Quote RFQ, click the "Get Quote" button for the product you need. Fill out the requested details and submit.
Yes, we do offer special pricing. Click on Get Quote for the product you need or email us at [email protected]
Typicaly 12-72 hours. However, it can take longer with some products. You are assigned a key account manager, who will keep you updated about the status of your request.
Yes. All our our products are purchased directly from the Manufacturer (or a pre-defined authorised channel). By default all warranties extended by the Manufacturer would extend to you as purchaser. And yes, we can provide a COC on request.